LeakPoint Leak Detection & Alarm Controller
The LeakPoint Leak Detection & Location Controller for continuous sensing-cable monitoring and accurate leak-position identification.
Supports up to 4 independent channels, sensitivity adjustment, 3 A relay output, NEMA 4X enclosure and RS485 Modbus communication.
Available with visual, audible or combined audible + visual alarm options for tanks, sumps, double-walled tanks and extended leak-detection cable runs.
Description
LeakPoint Leak Detection & Alarm Controller
The LeakPoint is an advanced leak detection and location controller designed not only to detect the presence of liquid but also to identify the leak position along the sensing cable.
Sensitivity adjustment provides fine tuning of the signal received from the sensing cable, while continuous cable monitoring enables rapid identification of leak events and faster localization of the affected area.
The LeakPoint Series is available in 1, 2, 3 or 4-channel configurations, allowing multiple independent sensing-cable runs to be monitored. RS485 Modbus communication supports integration with compatible PLC, SCADA, BMS and remote monitoring systems.
LeakPoint® features a 3 A relay output, NEMA 4X enclosure, optional visual and audible alarm configurations and Quick Connect cord grips for simplified installation.
Key Benefits
- Leak detection and location identification.
- Leak location accuracy of approximately ±0.9 m.
- Continuous sensing-cable monitoring.
- Sensitivity adjustment for signal fine tuning.
- Up to 4 independent detection channels.
- 3 A relay output.
- RS485 Modbus communication.
- NEMA 4X enclosure.
- Optional visual and / or audible alarm.
- Quick Connect cord grips.
Applications
- Tank and sump leak monitoring
- Double-walled tanks and interstitial monitoring
- Secondary containment areas
- Dual-containment piping
- Industrial facilities with extended sensing-cable runs
- Data centers and server rooms
- Manufacturing and storage facilities
Technical Specifications
| Specification | LeakPoint |
| Type | Leak Detection & Location Controller |
| Cable Sensing Range | Up to 150 m |
| Leak Location | Yes |
| Location Accuracy | Approx. ±0.9 m |
| Channels | 1 / 2 / 3 / 4 |
| Sensitivity Adjustment | Yes |
| Relay Output | 3 A |
| Communication | RS485 |
| Protocol | Modbus |
| Protection | NEMA 4X |
| Visual Alarm | Optional depending on version |
| Audible Alarm | Optional depending on version |
| Audible Silence | Available on applicable versions |
| Cable Connections | Quick Connect Cord Grips |
| Remote Monitoring | RS485 Modbus to compatible PLC / SCADA / BMS systems |
LeakPoint Models
| Model | Channels | Cable Inputs |
| LDP-100 | 1 | 1 |
| LDP-200 | 2 | 2 |
| LDP-300 | 3 | 3 |
| LDP-400 | 4 | 4 |
Alarm Options
| Suffix | Alarm Type |
| V | Visual Alarm |
| A | Audible Alarm |
| AV | Audible + Visual Alarm |
Example: LDP-200-AV = two-channel LeakPoint with audible and visual alarm.
IMPORTANT
The LeakPoint is a controller / alarm and is not the sensing element by itself. A compatible distance-locating sensing cable is required for actual leak detection and location.
For applications above 150m should be verified for the exact system configuration before selection.
![]()